intelligent PDU_ THREE PHASE switched PDU

11.52kW Switched Intelligent PDU, 250V (20 C13, 4 C19), 400V/32A Input, Remote Power Management via Ethernet, 6.6ft Cord, 1U Horizontal

Model Number: NKP-DY-TU-32a(ZN32-L20+H4-L2)

  • 11.52kW 16A 240V switched intelligent PDU
  • 1U horizontal rack-mount installation(brackets)
  • 24 outlet (20 C13, 4 C19 front), 1 plug (1 IEC320 60309 )
  • LED indicator for power and network status
  • Local/Remote current/ voltage/energy/temperature/humidity monitoring options
  • Remote control and monitor on PDU/outlets level options via Ethernet
Compare

产品描述


Intelligent PDU(Power Distribution Unit)

Features & FunctionsMeteredMonitoredSwitched
reliable power distribution
local power meter(A/V)optional
local ENV meter(Temp./RH)optionaloptionaloptional
remote power monitoring via network (A/V/KWh...) optional
remote ENV monitoring via network (Temp./RH) optionaloptional
remote switch/control on PDU level via network
remote switch/control on outlets level via network optional

 

Brief Introduction

KEJIA NKP-DY-TU series switched intelligent PDUs(Power Distribution Units) offer real-time monitoring on electricity factors for critical IT equipments via local digital meter or remote network systems. Power alert or event log supports custom notification of user-specified remote conditions via email, SNMP, Web, DHCP interface. Ensures a safer, greener and more convenient power distribution environment in unmanned server rooms, data centers, network closets, etc. High-quality design includes AL housing and standard 19” rack mount installation.

 

Main Features

  • 11.52kW 16A 240V switched intelligent PDU
  • 1U horizontal rack-mount installation(brackets)
  • 24 outlet (20 C13, 4 C19 front), 1 plug (1 IEC320 60309 )
  • Power Monitor: Total and each outlet power monitoring by Web, SNMP,
  • Protocols: HTTP, HTTPS, IPMI, SMASH-CLP, SSH, TELNET, SNMP
  • Outlet Control: Individual, Group, Schedule, Auto Ping
  • ENV: RJ11interfce for ambient temperature and humidity monitoring
  • Current Meter: Built-in web server to meter/display its current consumption
  • kWh Meter: Power consumption meter in kWh, easy for bill calculating
  • Power Delay: Power On/Off sequence can be defined
  • Alarm Thresholds: User-defined alarm thresholds for warning and overload
  • Event Alert: Email, Trap, Audible Alarm

 

Typical Application

Ideal for network configurations in datacenters and heavily configured equipment racks.

 

Product Parameter

Model No.NKP-DY-TU-32a(ZN32-L20+H4-L2)
PDU TypeIntelligent PDU/Switched
INPUT
Nominal Input Voltage400V
Maximum Input Current32A
Input Receptacles(1) IEC 320 60309
Inlet TypeIEC 320 60309 (3P, 32A/440V), blue
Input Cord Length(m/ft)2 m/6.6ft (standard)
Input Phase3 phase/Three phase
OUTPUT
Output Capacity11.52kVA(415/240V), 11.04kVA(400/230V), 1.056kVA(380/220V) 10A max per C13, 16A max per C19,
Frequency 50/60Hz
Output Receptacles(20) C13, (4)C19
Output Nominal VoltageSingle phase 240V(415V), 230V(400V), 220V(380V)
Output Maximum Current16A
Outlet TypeIEC320 C13, IEC320 C19
CIRCUIT PROTECTION
Overload ProtectionN/A
LED IndicatorSSL: (1) YELLOW LED
DHCP: (1) GREEN LED
INPUT STATUS:(1) RED LED
COMMUNICATION
Network ProtocolHttp(s), IPMI, SMASH-CLP, SSH, Telnet, SNMP
Network InterfaceRS232 connector to Ethernet
Environmental Interface (1) RJ11 for ENV (extensional)
Energy MeteringVoltage(V),Current(A), Energy(kWh)
Metering Range and AccuracyVoltage: ± 2% @ 90V~260V
Current: ±2%/±-0.1AMP @ 0A ~ 20 A
Energy(kWh): Range: 0.001kWh ~ 99999.999kWh; Precision: ±2% @ 50W~5000W, kh=1.0
Onboard Display 3 Digital Seven-segments for True RMS Meter
Function Button● Press and hold the key after 1 beeping, meter will show up branch current, temperature and humidity information in sequence.
● Press and hold the key after 2 beeping, meter will show up the IP address.
● Press and hold the key after 4 beeping, it can change the way to get IP by DHCP or Fixed IP.
● Press and hold the key after 6 beeping, it can reset PDU back to default setting.
Audible Alarm ● Warning-1 beep in 1 second.
● Overload-3 beeps in 1 second.
● Note: The audible alarm will keep beeping until the current is lower than 0.5 Amp for the threshold of warning and overload.
OPERATIONAL ENVIRONMENT
Operating Temperature Range 0℃-40℃(0℉-104℉)
Storage Temperature Range 0℃-40℃(0℉-104℉)
Relative Humidity(RH)0%-90%
Operating Elevation<3000m(9873ft)
PHYSICAL
Housing MaterialAluminum alloy
Housing ColorBlack
Unit Dimension(HWD/mm) -
Unit Weight(NW/kg) -
Shipping Dimension(HWD/mm) -
Shipping Weight(GW/kg) -
PDU Mounting Form1U Horizontal
ACCESSORIES
Package IncludesRack mounting brackets, product manual
TEST STANDARDS
Product TestCE-LVD, CE-EMC, RoHS-2011/65/EU compliant
CERTIFICATION
Regulatory Approvals CE, RoHS
WARRANTY
Product Warranty Period2-year warranty

 

 