产品描述
SWITCHED ATS/STS 32a
Brief Introduction
KEJIA NKP-DY-SU series ATS/STS(Automatic Transfer Switch) rack mount PDUs offer a redundant power option for single-corded network devices. Dual input cords support separate connection to primary and secondary power sources. The ATS/STS will normally supplies continuous power to all outlets as derived from the primary mains. If the primary power source becomes unstable or failed, the ATS/STS will switch over automatically to the secondary power source until the primary input is restored and stable. Super-fast switchover between primary and secondary power sources occurs within milliseconds, ensuring an uninterrupted power supply in data centers, telecom rooms, hospitals, banks, etc.
Main Features
- Dual input powers provide automatically redundant power protection.
- Built-in web server to manage PDU by network in real time
- Provide voltage, frequency, power factor, active power, apparent power and kWh information
- True RMS Current Meter
- Local LED Displays Amps, IP Address
- 10 Base-T Ethernet Port
- IPv4 Support
- SNMP Support (v1)
- SSL Web Browser (Https) for Set Up and Operation
- Alarm Notification via Email and SNMP
- User Defined Alarm Thresholds
- Circuit Breaker Protection
- Connect up to 1 Temperature and Humidity Probe
Typical Application
Auto-Transfer Switch/Switched ATS/STS PDU is ideal for providing switched outlet functionality and redundant A/B power to single-corded network equipment
Product Parameter
Model No. | NKP-DY-TSU-32a(ZN32-L52-2L2H) |
---|---|
Model No. | NKP-DY-TSU-32a(ZN32-L52-2L2H) |
PDU Type | ATS/STS/switched |
GENERAL | |
Operation Voltage | 220V-230V, single phase |
Max. Input Current | 32A |
Output Receptacles | (10) C13 10A/250V |
Power Cord | (2) cable to IEC309 32A 2P+E connector, 2m |
Frequency | 50/60Hz |
FUNCTION | |
(A: primary power source, B: secondary power source ) - both primary (A) and secondary (B) power sources are available. A is set as default mains. If A becomes unstable or failed, it will switch over automatically to B until A is restored and stable | |
Transfer Time | 8-16ms |
Network Protocol | Http(s), SNMP, DHCP,UDP |
Network Interface | RJ45 connector to Ethernet |
Energy Metering | Voltage(V),Current(A), Active Power(kW), Apparent Power(kVA), Energy(kWh), Frequency |
Voltage | ± 2% @ 90V~260V |
Active Power | ± 2% @ 50W~5000W |
Apparent Power | ± 2% @ 50VA~5000VA |
Frequency | ± 2% @ 45~65Hz |
Power Factor | ± 0.02 @ 0.5~1.0 |
Energy(kWh) | Range: 0.001kWh ~ 99999.999kWh; |
Precision: ±2% @ 50W~5000W, kh=1.0 | |
Current | ±2%/±-0.1AMP @ 0A ~ 32 A |
Onboard Display | 3 Digital Seven-segments for True RMS Meter |
Environmental Metering | Temperature, Humidity (±2%/±0.1) |
Environmental Interface | (1) RJ11 for ENV probe connection |
Overload Protection | (2) Circuit breaker 16A |
LED Indicator | SSL: (1) YELLOW LED; DHCP: (1) GREEN LED |
INPUT STATUS:(2) RED LED | |
OUTPUT STATUS:(2) GREEN LED | |
PHYSICAL | |
Operating Temperature Range | 0℃-40℃(0℉-104℉) |
Storage Temperature Range | 0℃-40℃(0℉-104℉) |
Relative Humidity(RH) | 0%-90% |
Operating Elevation | <3000m(9873ft) |
Housing Material | Aluminum alloy, black |
Unit Dimension(HWD/mm) | 432*44.5*260, 1U |
Unit Weight(NW/kg) | 7 |
PDU Mounting Form | Horizontal |
ACCESSORIES | |
Package Includes | Rack mounting brackets, product manual |
TEST STANDARDS | |
Product Test | CE-LVD, CE-EMC, RoHS-2011/65/EU compliant |
WARRANTY | |
Product Warranty Period | 2-year warranty |
用户评论