RS422 digital surge arrester NKP-TEL-3J-3
RS422 digital surge arrester NKP-TEL-3J-3 2RS422 digital surge arrester NKP-TEL-3J-3

RS422 Digital Signal Surge Protective Devices(SPD), Terminal Block NKP-TEL-3J-3

RS422, digital signal surge protection, terminal blocks, DIN rail

  • RS422 serial surge protector
  • Terminal connector
  • Ultrafast response time <1ns
  • Industrial thermal plastic enclosure
  • Systematic use of MOV, 3-pole gas tube and fast clamping diode

 

 

Compare
编码: piece 分类: 标签: , , ,

产品描述


 

NKP-TEL-3J-3

The NKP-TEL-3J-3 surge protector is designed to protect serial communication data processing equipments, connected to serial RS422 network. Featured with in/out terminals connector. It uses a combination of MOV, 3-electrode gas discharge tube and fast clamping diodes to provide large discharge current capacity and ultrafast response time. It’s for use as secondary surge protection at the equipment level behind a primary protection environment.

 

Main Features

  • RS422 serial surge protector
  • Terminal connector
  • Ultrafast response time <1ns
  • Industrial thermal plastic enclosure
  • Systematic use of MOV, 3-pole gas tube and fast clamping diode

 

Product Parameter

Model No.NKP-TEL-3J-3
ELECTRICAL CHARACTERISTICS
Typical ApplicationRS422 signal system
Nominal Operation Voltage(Un)12Vdc
Maximal Operation Voltage (Uc)24Vdc
Nominal Discharge Current (In) 5kA (8/20μs)
Maximal Discharge Current (Imax) 10kA (8/20μs)
Voltage Protection Level (Up) [X-X:10kV/5kA]≤1.0kV
Response Time (tA)1ns
Insertion Loss≤0.3dB (10MHz)
MECHANICAL CHARACTERISTICS
Max. Transmission Rate10Mbps
I/O Connectorterminal blocks
Protection Circuit4 pins
Failure Indicator/
Place of Installationindoor
Mounting35mm2 DIN rails acc. to EN 60715
Enclosure Materialthermoplastic, PA66
Enclosure Color green
Degree of ProtectionIP20
Test StandardGB/T18802.21/IEC61643-21
ENVIRONMENTAL CHARACTERISTICS
Stocking Temperature -5℃~+40℃ (-41℉-104℉)
Operating Temperature-20℃~+70℃ (-68℉-158℉)
Relative Humidity (RH)5% - 95% (non-condensing)
Operating Altitude <3000m (9843ft)
Dimension(L*W*H) 80mm*30mm*69mm
Weight(G/W)

 

 

Electrical Diagram

electrial diagram - RS422 digital signal surge protector, terminals, NKP-TEL-3J-3

 

 Wiring Diagram

wiring diagram - rs422 digital signal surge arrester NKP-TEL-3J-3

 

Dimension

size - digital surge suppressor NKP-TEL-3J-3

 *Installation Notes

  1. Must disconnect power before installation, no hot-line operation is allowed, and better to under the guidance of professional electrician.
  2. For best performance, mount protector in serial with the equipment it is protecting as close as possible, and better to install one protector at each end of the data line.
  3. The ground wire on the product (if included) must be attached directly to the metal chassis of the equipment to be protected. The length of the grounded wire is not to exceed 11 inches.
  4. No special maintenance is needed, however regular inspection is needed, especially during storm seasons.

 

00 Model Selection Table

Model No.NKP-TEL-3J-2(dual)NKP-TEL-3J-2(single)
ELECTRICAL CHARACATERISTICS
Typical ApplicationRS485 signal system
Nominal Operation Voltage(Un)22.5Vdc
Maximal Operation Voltage (Uc)24Vdc
Nominal Discharge Current (In) 5kA (8/20μs)
Maximal Discharge Current (Imax) 10kA (8/20μs)
Voltage Protection Level (Up) [X-X:10kV/5kA]≤1.0kV
Response Time (tA)1ns
Insertion Loss≤0.3dB (10MHz)
Max. Transmission Rate10Mbps
MECHANICAL CHARATERISTICS
I/O Connector terminal blocks
Protection Circuit2 lines, 4 pins1line, 2 pins
Failure Indicator/
Place of Installationindoor
Mounting35mm2 DIN rails acc. to EN 60715
Enclosure Materialthermoplastic, PA66
Enclosure Color green
Degree of ProtectionIP20
Test StandardGB/T18802.21/IEC61643-21
ENVIRONMENTAL CHARACTERISTICS
Stocking Temperature -5℃~+40℃ (-41℉-104℉)
Operating Temperature-20℃~+70℃(-68℉-158℉)
Relative Humidity (RH)5% - 95% (non-condensing)
Operating Altitude<3000m (9843ft)
Dimension(L*W*H) 80mm*30mm*69mm80mm*20mm*69mm
Weight(G/W)

用户评论

目前还末有评论

我要第一个评论! “RS422 Digital Signal Surge Protective Devices(SPD), Terminal Block NKP-TEL-3J-3”